Frequently asked questions

What Dragon Jacket is made of, how it performs, how it installs and how to order it.

Product

5 questions

What is Dragon Jacket made of?

A closed-cell polyisocyanurate (polyiso) foam core, fully encapsulated in polyurea at our plant in Post Falls, Idaho. The polyurea encapsulation is 60 mils thick and covers every surface of each half of the component, the mating faces included.

Pipe support inserts use high-density 4, 6 or 8 lb cores under the same polyurea encapsulation.

What components do you make?

Straight sections in 36″ lengths, elbows, tees, flanges, valves, bell connections, mechanical joints, grooved couplings and pipe support inserts. Each component is made to fit the pipe or fitting it covers.

We also make custom components for strainers, pump volutes and other equipment. See pipe insulation.

What pipe can it be used on?

Ductile iron, cast iron, steel, HDPE and PVC, whether the joints are bell and spigot, fused or mechanical, grooved, or welded and flanged.

What sizes and thicknesses are available?

Standard components are made for 1/2″ to 60″ NPS pipe, and other sizes are made to order.

Insulation thickness is 1, 1-1/2, 2 or 3″. We size the thickness to each project’s freeze protection, heat loss or condensation requirement.

Is Dragon Jacket made in the USA?

Yes. Dragon Jacket is manufactured in Post Falls, Idaho. We supply Build America, Buy America (BABA) documentation for federally funded projects.

Performance

10 questions

What is the R-value?

R-6.25 per inch for the standard 2 lb core when new, a thermal conductivity of 0.160 Btu·in/hr·ft²·°F (ASTM C518). Like all polyiso, the core ages to a slightly lower R-value, so we use 0.19 in our heat loss and freeze time calculations.

Try the pipe freeze time calculator or see the full technical data.

What temperatures can it handle?

−40°F to 300°F continuous, and up to 350°F intermittent.

Is it waterproof?

Water can’t soak into it. The polyurea encapsulation covers every surface of the foam, and the closed-cell core absorbs less than 0.6% water by volume (ASTM C272).

Does it need a vapor barrier or jacketing?

No. The polyurea encapsulation is both the jacketing and the vapor retarder, with a water vapor transmission of 0.64 grains/hr·ft² or less (ASTM E96). It suits chilled water and condensation control.

Joints close with the factory-molded overlap and banding. Where a field cut exposes the foam, seal the cut face. On below-ambient lines, size the thickness to keep the surface above the dew point, and follow the installation tips at terminations and supports.

For very high vapor drive service, such as ammonia refrigeration, ask us first.

How does it keep water off the pipe?

Straights install with the seam facing down. Water that gets under the insulation, from outside or from a leaking pipe, drains out at the seam instead of collecting against the pipe, and a leak shows at the seam where it can be seen. See corrosion under insulation.

Can it be buried?

Yes. For direct burial we recommend the 4 lb high-density core, with a compressive strength of 72.5 psi (ASTM D1621). With the standard 2 lb core, the trench should be prepared to ASTM D2321 Class II.

How does it hold up outdoors?

The polyurea encapsulation is suitable for outdoor exposure and has an impact resistance of 320 in-lb (ASTM D2794). Add a UV-stable topcoat where color or gloss retention matters. See durability.

What is the fire rating?

The standard polyurea encapsulation is not fire rated. A fire-rated polyurea is available, with a flame spread index of 25 maximum and a smoke developed index of 250 maximum (ASTM E84). Tell us if your specification calls for a rating.

Is it chemical resistant?

The polyurea encapsulation is rated against 36 common chemicals, from bleach and diesel to sulfuric acid and sea water, after a 7-day immersion test. See the chemical resistance ratings.

Can it be heat traced?

Yes, two ways. [Q]Core has heat trace built into the straights at our plant and runs on 120 V. Or order the insulation sized for trace, with room for a field-installed heat trace cable.

Installation

5 questions

How is it installed?

Each component opens like a clamshell. Place it over the pipe with the seam facing down, close it and band it. Each straight has a built-in overlap that laps the next one, so there is no mastic and no field-applied jacketing.

It installs with hand tools and doesn’t need an insulation contractor. General construction crews, plant maintenance staff and ship crews have all installed it. At the City of Asheboro, NC, four maintenance staff with no insulating experience stripped the old insulation and installed Dragon Jacket in one 12-hour day. See easy installation.

How is it secured?

With 304 stainless steel bands. The ball-lock buckle is pulled tight with a banding tool and the band is trimmed. Other banding can be used where the application allows.

Can it be removed and reinstalled?

Yes. Cut the bands, open the component, do the work, then close it and re-band it with new bands. Inspections and repairs don’t mean replacing the insulation. On the Stolt Tankers hot water lines, the ship’s crew removes and reuses it themselves.

Can it tie into existing insulation?

Yes. Where Dragon Jacket meets another insulation system, a polyurea strip or tape is applied over the joint and banded on both sides. Most projects use Dragon Jacket for the whole line.

Do you install it?

Most customers install it with their own crews. If you’d like installation included, tell us when you request a quote.

Ordering

4 questions

How do I get pricing?

Send us a drawing set, takeoff or CAD files, or photos and measurements, along with the pipe size and material, the operating temperature and whether the line is heat traced. Most quotes go out within one to two business days. Request a quote.

Do you need to visit the site?

No. We design from drawings, takeoffs, measurements and photos, or a 3D scan. The Floriston, CA project was designed from the contractor’s measurements and photos, and Children’s Services Council of Palm Beach County from the customer’s 3D scan of the site.

What is the lead time?

It depends on the size of the order and the plant schedule, and we confirm it on every quote. Smaller orders can be ready to ship within a week of the order.

How do engineers specify it?

Our pipe insulation specification is written in CSI format as Section 23 07 19 and is available in Word and PDF. For engineers has the technical data, specification and calculators in one place.

No questions match. Ask us directly and we’ll answer it.